Checking With Expansion Valve, Reservoir And A/C Compressor Regulator Valve N280

2007 Volkswagen GTI FahrenheitSECTION Checking With Expansion Valve, Reservoir And A/C Compressor Regulator Valve N280
NOTE:

Connecting service station, refer to SERVICING STATION, CONNECTING FOR MEASURING AND TESTING .

Observe test requirements, refer to PRESSURES, CHECKING .

-- Bring engine speed up to 2000 RPM.

-- Check the pressure gauge on the A/C service station.

NOTE:

Switching pressures for actuation of A/C compressor regulator valve -N280- and radiator fan -V7- are vehicle-specific.

The pressure should be measured at the service connections. The location of these connections depends on the vehicle. Refer to [For engine(s) BGP, BPY, BGQ, CBTA, CBUA, CCTA, CBFA] Description and Operation .

Target values 

High-pressure side 

Increasing from initial pressure (when connecting pressure gauges) to 20 bar.

Low-pressure side 

Decreasing from initial pressure (when connecting pressure gauges) to the value in the graph.

Fig 1: Identifying Permissible Tolerance Range Graph
GWWA87-0377Courtesy of VOLKSWAGEN UNITED STATES, INC.

A - Low pressure (measured at service connection) in bar absolute

B - Control current for A/C Compressor Regulator Valve -N280-.

C - Permissible tolerance range

NOTE:

Under unfavorable conditions (very high ambient temperatures, high humidity), pressure on high-pressure side may increase to max. 29 bar.

The control current -B- is shown in the measured value block.

The high pressure measured from the High Pressure Sensor -G65- is not shown in the measured value block. Refer to [For engine(s) BGP, BPY, BGQ, CBTA, CBUA, CCTA, CBFA] Diagnosis and Testing .

Low pressure settles as a function of control current for A/C compressor regulator valve -N280- within compressor output range in tolerance range.

Under unfavorable conditions (very high ambient temperatures, high humidity), compressor output may not always be sufficient to attain the specified value.

The specified operating current for the regulator valve must be greater than 0.3 A in order to ensure reliable valve activation.

In the setting "maximum cooling output" control current is regulated to approximately 0.65 A up to 0.85 A (vehicle specific, displayed in measured value block). Refer to [For engine(s) BGP, BPY, BGQ, CBTA, CBUA, CCTA, CBFA] Diagnosis and Testing .

At absolute pressure, 0 bar corresponds to absolute vacuum. Normal ambient pressure corresponds to 1 bar absolute pressure. 0 pressure corresponds to an absolute pressure of one bar on most pressure gauges (indicated by -1 bar below 0).

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High pressure remains constant or increases only slightly (above pressure with engine stopped).
  • Low pressure quickly drops to value in graph or below.
  • Required cooling output is not attained
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
  • Not enough refrigerant in refrigerant circuit
-- Check activation of A/C Compressor Regulator Valve -N280-. -- Localize leak with leak detector and eliminate -- Charge the refrigerant circuit
  • High pressure normal.
  • Low pressure in line with value in graph.
  • Required cooling output is not attained
   
  • High pressure normal.
  • Low pressure too low (see Fig 1).
  • Required cooling output is not attained
  • Not enough refrigerant in refrigerant circuit
-- Extract refrigerant from refrigerant circuit
  • If quantity of refrigerant extracted is substantially less than specified capacity.
-- Localize leak with leak detector and eliminate. -- Charge the refrigerant circuit -- Repeat test
  • If quantity of refrigerant extracted roughly corresponds to specified capacity:
 
  • Expansion valve faulty
-- Replace expansion valve -- Charge the refrigerant circuit -- Repeat test
NOTE:

If no malfunction is found with this complaint, flush (clean) refrigerant circuit with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . If that is not possible in this workshop, flush the refrigerant circuit with compressed air and remove moisture with nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN .

Check measured values from Evaporator Vent Temperature Sensor -G263- or Evaporator Temperature Sensor -G308- and activation of A/C Compressor Regulator Valve -N280-. If the measured value of the High Pressure Sensor -G65- is faulty, the evaporator can ice up or the cooling output is not reached.

If the function of the air conditioning system is not OK when the test is repeated after replacing expansion valve, re-install old expansion valve and flush refrigerant circuit with compressed air and nitrogen. Then replace A/C compressor and reservoir.

With this malfunction, evaporator may ice up although quantity of refrigerant in circuit is OK.

If expansion valve is malfunctioning (permanently closed or does not open sufficiently), A/C compressor regulator valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Because refrigerant cannot flow through the expansion valve, the correct cooling output cannot be reached. The high pressure may not increase or may only increase slightly.

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High pressure only increases slightly above pressure with engine stopped.
  • Low pressure drops only slightly.
  • Required cooling output is not attained
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
-- Check activation of A/C Compressor Regulator Valve -N280-.
 
  • A/C compressor faulty.
-- Extract refrigerant circuit. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Replace A/C compressor. -- Charge the refrigerant circuit
  • High pressure increases above specification.
  • Low pressure quickly drops to value in graph or below.
  • Required cooling output is not attained
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
-- Check activation of A/C Compressor Regulator Valve -N280-.
 
  • Constriction or obstruction in refrigerant circuit
-- Run hand over refrigerant circuit to check for differences in temperature
  • If difference in temperature is found at one component:
-- Replace hose or pipe if kinked or constricted. -- In the event of an obstruction, flush refrigerant circuit with compressed air and nitrogen. -- Charge the refrigerant circuit -- Repeat test
  • If no malfunction can be found:
-- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Charge the refrigerant circuit. -- Repeat test if function is not OK.
 
  • Expansion valve malfunctioning
-- Extract refrigerant circuit. -- Replace expansion valve and receiver. -- Charge the refrigerant circuit
NOTE:

With this malfunction, evaporator may ice up although quantity of refrigerant in circuit is OK.

If expansion valve is malfunctioning (permanently closed or does not open sufficiently), A/C compressor regulator valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Because refrigerant cannot flow through the expansion valve, the correct cooling output cannot be reached. The high pressure may not increase or may only increase slightly.

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High and low pressure normal at first, after some time high pressure increases above specification.
  • After some time, low pressure decreases to graph value or lower.
  • Required cooling output is no longer attained.
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
-- Check activation of A/C Compressor Regulator Valve -N280-.
  • High pressure and lower pressure normal first, after a long period of driving, the low pressure falls below the specified value (evaporator iced up).
  • Moisture in refrigerant circuit
-- Extract refrigerant circuit. -- Refrigerant Circuit, Flushing with Compressed Air and Nitrogen. -- Replace reservoir with dryer. -- Evacuate refrigerant circuit for at least 3 hours. -- Charge the refrigerant circuit -- Repeat test, if function is not OK. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Charge the refrigerant circuit. -- Repeat test
NOTE:

If this complaint occurs after a long operating time or only sporadically (the low pressure falls under the specified value and the evaporator ices up), replacing the dryer (installed in the reservoir) is sufficient. The quantity of refrigerant oil should be adjusted. Refrigerant circuit is then to be evacuated for at least 3 hours.

First, it is not necessary to flush the refrigerant circuit with compressed air and nitrogen in case of this complaint because generally only a small amount of moisture is in the system and this can be removed by a long evacuation.

With this malfunction, evaporator may ice up although quantity of refrigerant in circuit is OK.

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High pressure normal, low pressure too low (see Fig 1), the necessary cooling output is not reached.
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
-- Check activation of A/C Compressor Regulator Valve -N280-.
 
  • Expansion valve malfunctioning
-- Extract refrigerant circuit. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Replace expansion valve and receiver. -- Charge the refrigerant circuit. -- Repeat test if function is not OK. -- Replace A/C compressor.
 
  • A/C compressor faulty.
-- Extract refrigerant circuit. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Replace A/C compressor. -- Charge the refrigerant circuit. -- Repeat test
NOTE:

Note the following when the malfunction "high pressure normal, low pressure too low" is detected: faulty, the evaporator can ice up or the cooling output will not be reached.

With this malfunction, evaporator may ice up although quantity of refrigerant in circuit is OK.

Check measured values from Evaporator Vent Temperature Sensor -G263- or Evaporator Temperature Sensor -G308- and activation of A/C Compressor Regulator Valve -N280-. If the measured value of the High Pressure Sensor -G65- is faulty, the evaporator can ice up or the cooling output is not reached.

If the problem is with the A/C Compressor Regulator Valve -N280- (regulating valve is not actuated but compressor operates nevertheless), refrigerant circuit does not have to be flushed. With this malfunction, replacing the A/C compressor is sufficient (adjust refrigerant oil quantity in new A/C compressor).

If expansion valve is malfunctioning (permanently closed or does not open sufficiently), A/C compressor regulator valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Because refrigerant cannot flow through the expansion valve, the correct cooling output cannot be reached. The high pressure may not increase or may only increase slightly.

Refer to [For engine(s) BGP, BPY, BGQ, CBTA, CBUA, CCTA, CBFA] Removal and Installation .

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High pressure normal or too high.
  • Low pressure too high (see Fig 1).
  • A/C compressor noise (particularly after switch-on).
  • Required cooling output is not attained
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
  • To much refrigerant in the circuit.
-- Check activation of A/C Compressor Regulator Valve -N280-. -- Extract refrigerant from refrigerant circuit
  • If quantity of refrigerant extracted roughly corresponds to specified capacity:
-- Replace A/C compressor.
  • If quantity of refrigerant extracted is substantially greater than specified capacity:
-- Charge the refrigerant circuit. -- Repeat test
 
  • To much refrigerant oil in the circuit.
-- Discharge refrigerant circuit
  • If quantity of refrigerant extracted roughly corresponds to specified capacity:
-- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Charge the refrigerant circuit. -- Repeat test
 
  • Expansion valve malfunctioning
-- Discharge refrigerant circuit. -- Replace expansion valve and receiver. -- Charge the refrigerant circuit. -- Repeat test if function is not OK. -- Replace A/C compressor.
 
  • A/C compressor faulty.
-- Discharge refrigerant circuit. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Replace A/C compressor.
  • If quantity of refrigerant extracted is substantially greater than specified capacity:
-- Charge the refrigerant circuit. -- Repeat test
NOTE:

If the problem is with the A/C Compressor Regulator Valve -N280- (regulating valve is not actuated but compressor operates nevertheless), refrigerant circuit does not have to be flushed. With this malfunction, replacing the A/C compressor is sufficient (adjust refrigerant oil quantity in new A/C compressor).

Overfilling with refrigerant oil can occur if, for example, the compressor has been replaced without adjusting the quantity of refrigerant oil.

If the A/C compressor is not replaced, the refrigerant oil should be drained from the A/C compressor via the oil drain plug. Out of the entire quantity of refrigerant oil MAINTENANCE, DIAGNOSIS , 50 grams should be put in the A/C compressor and the rest in the refrigerant circuit.

If expansion valve is malfunctioning (permanently closed or does not open sufficiently), A/C compressor regulator valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Because refrigerant cannot flow through the expansion valve, the correct cooling output cannot be reached. The high pressure may not increase or may only increase slightly.

Possible Deviation From Specification Possible Cause Of Fault Corrective Action
  • High and low pressure normal.
  • Required cooling output is not attained
  • Activation of A/C Compressor Regulator Valve -N280- is faulty.
  • To much refrigerant oil in the circuit.
-- Check activation of A/C Compressor Regulator Valve -N280-. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A .
  • High and low pressure normal.
  • A/C compressor noise (particularly after switch-on).
  • The required cooling performance is obtained
  • To much refrigerant oil in the circuit.
-- Discharge refrigerant circuit. -- Flush (clean) refrigerant circuit. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH REFRIGERANT R134A . -- Charge the refrigerant circuit -- Repeat test
 
  • Expansion valve malfunctioning
-- Replace expansion valve
NOTE:

Overfilling with refrigerant oil can occur if, for example, the compressor has been replaced without adjusting the quantity of refrigerant oil.

If the A/C compressor is not replaced, the refrigerant oil should be drained from the A/C compressor via the oil drain plug. Out of the entire quantity of refrigerant oil, 50 grams should be put in the A/C compressor and the rest in the refrigerant circuit. Refer to MAINTENANCE, DIAGNOSIS

If expansion valve is malfunctioning (permanently open), evaporator temperature is no longer regulated such that only refrigerant in gaseous state exits from the evaporator. Under certain usage conditions, liquid droplets may then be drawn in by the compressor and cause noise (liquid cannot be compressed).

RENDER: 1.0x

NO RELATED

Recommended Tools & Savings

Use the Manual With the Right Hardware

Pair factory procedures with proven DIY tools so the instructions are easier to execute.

Affiliate disclosure: We may earn a commission at no extra cost to you.

When to See a Mechanic

Stop DIY work and contact a certified mechanic immediately if any of the following apply:

  • You smell fuel, burning insulation, or see smoke.
  • Brakes feel soft, pull hard to one side, or make grinding noises.
  • The engine overheats, stalls repeatedly, or misfires under load.
  • You are missing required tools, torque specs, or safe lifting equipment.
  • You are not confident in the next step or safety outcome.