Monitor Result

2009 Toyota Sienna XLE, FWDSECTION Monitor Result

Refer to Checking Monitor Status for detailed information (See CHECKING MONITOR STATUS ).

The test value and test limit information are described as shown in the following table. This information is included in Monitor Result of the emissions-related DTC sections:

  • MID (Monitor Identification Data) is assigned to each emissions-related component.
  • TID (Test Identification Data) is assigned to each test value.
  • Scaling is used to calculate the test value indicated on generic OBD II scan tools.

Thermostat 

THERMOSTAT SPECIFICATION

MID TID Scaling Description of Test Value Minimum Test Limit Maximum Test Limit
$3D $C9 Multiply by 0.01 [kPa] Test value for small leak (P0456)
Refer to pressure D(1)
Minimum test limit for small leak Maximum test limit for small leak
$3D $CA Multiply by 0.01 [kPa] Test value for gross leak (P0455)
Refer to pressure E(1)
Minimum test limit for gross leak Maximum test limit for gross leak
$3D $CB Multiply by 0.01 [kPa] Test value for vacuum pump stuck OFF (P2401)
Refer to pressure A(1)
Minimum test limit for vacuum pump stuck OFF Maximum test limit for vacuum pump stuck OFF
$3D $CD Multiply by 0.01 [kPa] Test value for vacuum pump stuck ON (P2402)
Refer to pressure A(1)
Minimum test limit for vacuum pump stuck ON Maximum test limit for vacuum pump stuck ON
$3D $CE Multiply by 0.01 [kPa] Test value for vent valve stuck OFF (vent) (P2420)
Refer to pressure C(1)
Minimum test limit for vent valve stuck ON Maximum test limit for vent valve stuck ON
$3D $CF Multiply by 0.01 [kPa] Test value for vent valve stuck ON (P2419)
Refer to pressure A(1)
Minimum test limit for vent valve stuck OFF Maximum test limit for vent valve stuck OFF
$3D $D0 Multiply by 0.01 [kPa] Test value for 0.02 inch orifice low flow (P043E)
Refer to pressure B(1)
Minimum test limit for 0.02 inch orifice low flow Maximum test limit for 0.02 inch orifice low flow
$3D $D1 Multiply by 0.01 [kPa] Test value for 0.02 inch orifice high flow (P043F)
Refer to pressure A(1)
Minimum test limit for 0.02 inch orifice high flow Maximum test limit for 0.02 inch orifice high flow
$3D $D4 Multiply by 0.01 [kPa] Test value for purge VSV stuck closed (P0441)
Refer to pressure F(1)
Minimum test limit for purge VSV stuck closed Maximum test limit for purge VSV stuck closed
$3D $D5 Multiply by 0.01 [kPa] Test value for purge VSV stuck open (P0441)
Refer to pressure E(1)
Minimum test limit for purge VSV stuck open Maximum test limit for purge VSV stuck open
$3D $D7 Multiply by 0.01 [kPa] Test value for purge flow (P0441)
Refer to pressure G(1)
Minimum test limit for purge flow Maximum test limit for purge flow
(1) Pressures A to G are indicated as shown in the diagram below.
Fig 1: Blinking Pattern Of Purge Flow Monitor
G05128658Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
RENDER: 1.0x

NO RELATED

Recommended Tools & Savings

Use the Manual With the Right Hardware

Pair factory procedures with proven DIY tools so the instructions are easier to execute.

Affiliate disclosure: We may earn a commission at no extra cost to you.

When to See a Mechanic

Stop DIY work and contact a certified mechanic immediately if any of the following apply:

  • You smell fuel, burning insulation, or see smoke.
  • Brakes feel soft, pull hard to one side, or make grinding noises.
  • The engine overheats, stalls repeatedly, or misfires under load.
  • You are missing required tools, torque specs, or safe lifting equipment.
  • You are not confident in the next step or safety outcome.