1987 Oldsmobile ToronadoFACTORY OEM SERVICE PROCEDURE

Chart 10, A/C System Performance Test: Notes

SYSTEM PERFORMANCE CHART (AT 70°F/21°C AMBIENT AIR TEMPERATURE)

Application Specification
Ambient Air in Degrees °F/°C 70°F/21°C
Hi Side Pressure (1) 149 PSI
Pressure Plus and/or Minus 20 PSI (+/- 140 kPa) 1025 kPa
Lo Side Pressure (1) 25 PSI
Pressure Plus and/or Minus 2 PSI (+/- 8 kPa) 170 kPa
Center A/C Outlet Temperature (2) (+/- 2°F (1°C)) 50°F (10°C)
(1) Pressure reading taken just before Compressor Clutch releases.
(2) Outlet temperature will be higher on humid days.
SYSTEM PERFORMANCE CHART (AT 80°F/27°C AMBIENT AIR TEMPERATURE)

Application Specification
Ambient Air in Degrees °F/°C 80°F/27°C
Hi Side Pressure (1) 178 PSI
Pressure Plus and/or Minus 20 PSI (+/- 140 kPa) 1225 kPa
Lo Side Pressure (1) 27 PSI
Pressure Plus and/or Minus 2 PSI (+/- 8 kPa) 185 kPa
Center A/C Outlet Temperature (2) (+/- 2°F (1°C)) 52°F (11°C)
(1) Pressure reading taken just before Compressor Clutch releases.
(2) Outlet temperature will be higher on humid days.
SYSTEM PERFORMANCE CHART (AT 90°F/32°C AMBIENT AIR TEMPERATURE)

Application Specification
Ambient Air in Degrees °F/°C 90°F/32°C
Hi Side Pressure (1) 214 PSI
Pressure Plus and/or Minus 20 PSI (+/- 140 kPa) 1475 kPa
Lo Side Pressure (1) 29 PSI
Pressure Plus and/or Minus 2 PSI (+/- 8 kPa) 200 kPa
Center A/C Outlet Temperature (2) (+/- 2°F (1°C)) 54°F (12°C)
(1) Pressure reading taken just before Compressor Clutch releases.
(2) Outlet temperature will be higher on humid days.
SYSTEM PERFORMANCE CHART (AT 100°F/38°C AMBIENT AIR TEMPERATURE)

Application Specification
Ambient Air in Degrees °F/°C 100°F/38°C
Hi Side Pressure (1) 272 PSI
Pressure Plus and/or Minus 20 PSI (+/- 140 kPa) 1875 kPa
Lo Side Pressure (1) 33 PSI
Pressure Plus and/or Minus 2 PSI (+/- 8 kPa) 230 kPa
Center A/C Outlet Temperature (2) (+/- 2°F (1°C)) 56°F (13°C)
(1) Pressure reading taken just before Compressor Clutch releases.
(2) Outlet temperature will be higher on humid days.
FREON PRESSURE/TEMPERATURE RELATIONSHIP CHART - LOW SIDE (1)

Pressure (PSI) Tempurature °F (°C)
50 53 (12)
52 55 (13)
54 57 (14)
56 59 (15)
58 60 (15.5)
60 62 (16.6)
62 64 (18)
64 65 (18.5)
66 67 (19.5)
68 68 (20)
70 70 (21)
72 72 (22)
74 74 (23.5)
76 75 (24)
78 76 (24.5)
80 77 (25)
82 79 (26)
85 81 (27)
88 83 (28.5)
90 84 (29)
92 85 (29.5)
95 87 (30.5)
98 89 (31.5)
100 90 (32.5)
102 91 (33)
105 93 (34)
108 95 (35)
110 96 (35.5)
112 97 (36)
115 99 (37)
118 101 (38.5)
120 102 (39)
125 104 (40)
130 107 (42)
135 109 (43)
140 112 (44.5)
(1) A/C Low Side BD 28 check made after 5 minutes with engine "OFF". A given pressure should correspond to a temperature reading plus and/or minus 6°F of the specified value.
Factory Service Tools

Use the Manual With the Right Hardware

Pair factory procedures with proven DIY tools so the instructions are easier to execute.

Disclosure: Verified tool recommendations may earn an affiliate commission at no cost to you.

When to See a Mechanic

Stop DIY work and contact a certified mechanic immediately if any of the following apply:

  • • You smell fuel, burning insulation, or see smoke.
  • • Brakes feel soft, pull hard to one side, or make grinding noises.
  • • The engine overheats, stalls repeatedly, or misfires under load.
  • • You are missing required tools, torque specs, or safe lifting equipment.
  • • You are not confident in the next step or safety outcome.